Model (Global Code) |
GP2501-LG41-24V (PFXGP2501LD)
|
Type |
Monochrome LCD |
Display Colors |
Black and White (2 Shades)/ Black and White (8 Shades)
(software control) |
Backlight |
CCFL (Service life: more than 50,000 at 24 hr. operation) |
Resolution |
640 × 480 pixels |
Effective Display
Area (mm) |
211.2(W) [8.34 in.] × 158.4(H)mm [6.24 in.] |
Brightness Control |
4 levels of adjustment available via touch panel |
Contrast Control |
8 levels of adjustment available via touch panel |
Language Character Sets |
ASCII: (Code page 850) Alphanumeric (incl. European characters)
Chinese: (GB2312-80 codes) simplified Chinese fonts
Japanese: ANK 158, Kanji : 6962 (JIS Standards 1 & 2)
Korean: (KSC5601 - 1992 codes) Hangul fonts
Taiwanese: (Big 5 codes) traditional Chinese fonts |
Text |
8 × 8 dots |
80 char. × 60 rows |
8 × 16 dots |
80 char. × 30 rows |
16 × 16 dots |
40 char. × 30 rows |
32 × 32 dots |
20 char. × 15 rows |
Character Sizes*1 |
8 × 8 dots, 8 × 16 dots, 16 × 16 dots, 32 × 32 dots |
Font Sizes |
Height can be expanded 1 to 8 times.
Width can be expanded 1/2 *2, 1 to 8 times. |
Application Memory |
2MB FLASH EPROM |
Data Backup Memory |
128KB - uses lithium battery *3 |
Touch Panel Resolution |
32 × 24 keys/ screen - 1 or 2 point touch |
External
Interfaces |
Serial Interface |
Asynchronous Transmission: RS232C/ RS422
Data Length: 7 or 8 bits
Stop Bit: 1 or 2 bits
Parity: None, Odd or Even
Data Transmission Speed: 2400 to 115.2kbps, 187.5Kbps*4 |
Tool Connector |
Asynchronous TTL level nonprocedure command I/F
Used for transferring data between the GP application software and the GP.
Used for data transfer with the 2-Port feature.
Used for a variety of devices, including a bar-code reader. |
CF Card Interface |
1 slot |
Printer Interface |
Compatible with NECPC-PR201/PL, EPSON ESC/P24-J84(C), HP Laser Jet, PCL 4 command, EPSON PM/Stylus (6-color ink), EPSON Stylus (4-color ink) compatible printers*5 |
AUX
Input/Output *6 |
Remote
Reset
Input |
Remote Reset Input: 1 point
Input Voltage: DC24V ±10%
Input Current: 4mA (TYP)
Min. Input Pulse Width: 2ms
Operating Voltage: (When ON) Min. DC21.1V/
(When OFF) Max. DC3V
Isolation Method : Photocoupler Isolation
|
Output |
Output: 3 Points
(RUN Output: 1 point, System Alarm Output: 1 point,
External Buzzer Output: 1 point)
Rated Voltage: DC24V,
Max. Rated Current: 50mA/ point,
Wire Gauge: AWG28 to AWG16
|